SK80-F-T-PMO-5 - KNX Fill Level Meter for Oil Tanks, Hydrostatic Sensor with Temp, up to 5 m (16.4 ft)

SKU: 30807370
✗ UL Listed
This product has not been certified by an NRTL (UL, ETL, CSA or equivalent). Installation in USA projects may require a Field Evaluation by a recognized laboratory. Consult your local AHJ before specifying.
~ Low Voltage · SELV
This device operates on a Safety Extra Low Voltage circuit — such as the KNX 29V bus or a DALI 16V bus (NEC Class 2). When powered by an NRTL-listed power supply, many AHJs accept non-listed SELV devices. Verify with your local AHJ before specifying.
Regular price $653.53 USD
Regular price -31% $941.08 USD Sale price $653.53 USD
In stock
On backorder
KNX & DALI Specialists

Not sure which device fits your project? Our team speaks KNX. Contact us for a free technical recommendation.

Free shipping over $500
KNX certified devices
Expert technical support

The SK80-F-T-PMO-5 is a KNX fill-level meter for oil tanks. It combines the SK80-F control unit with a hydrostatic Modbus sensor that also measures temperature, for fill heights up to 5000 mm (196.9 in) on a 10 m (32.8 ft) cable. Specified media are heating oil, diesel, vegetable oil and lubricating oil.

Values are shown locally and sent to KNX, with a potential-free switch output for upper and lower limits. The system runs on KNX bus power. Not for use in explosive (EEx) zones.

Key Features

  • Hydrostatic sensor with temperature, 0 to 5000 mm (0 to 196.9 in), Modbus RS485, accuracy 0.5 % FS
  • Submersible sensor 27 x 132 mm (1.06 x 5.2 in), IP68, 10 m (32.8 ft) cable
  • Media: heating oil, diesel, vegetable oil, lubricating oil (not for EEx zones)
  • Fill level in m³, level, distance and %, resolution 1 mm (0.04 in); local display
  • Potential-free limit-value switch output (20 mA); ETS application SK80_F
  • Control unit 120 x 90 x 50 mm (4.72 x 3.54 x 1.97 in), IP65; bus powered (approx. 400 mW), no auxiliary supply

Technical Specifications

Article no. 30807370
KNX bus voltage KNX 21-32 VDC, approx. 20 mA
Power consumption approx. 400 mW from KNX bus
Auxiliary supply None – no additional voltage required (sensor head fed 13 V / 20 mA max from the unit)
Measuring Fill level in m3, level, distance and %; resolution 1 mm (0.04 in); sensor accuracy 0.5 % FS; ultrasonic 300-5000 mm (11.8 to 196.9 in), hydrostatic 0-5000 / 0-10000 mm (0 to 393.7 in)
Inputs / outputs & connections Sensor inputs 0-1 V, 0-5 V, 0-10 V, 4-20 mA (100 Ohm shunt), Modbus RTU RS485; potential-free switch output 20 mA, 5-230 V AC/DC tied to upper/lower limits; KNX terminal red/black; integrated display
Protection rating IP65
Dimensions 120 x 90 x 50 mm (4.72 x 3.54 x 1.97 in)
Mounting Wall/surface mount with screws; grey plastic housing with clear cover
Operating temperature -20 to +55 °C (-4 to 131 °F) (storage -20 to +85 °C (-4 to 185 °F)), 0-95 % RH non-condensing; ultrasonic head -10..+50 °C (14 to 122 °F), hydrostatic head 0..+60 °C (32 to 140 °F)

Downloads

(CE certified; not UL/NRTL listed — verify local code requirements before specifying in US installations)

Orders over $500 ship free within the USA (under 50 lbs). Orders under $500 carry a low cost shipping fee.

Most in-stock orders ship within 1–2 business days from Miami, FL. Delivery typically takes 3–5 business days depending on destination.

For freight or oversized orders, our team will contact you with a custom quote.

All KNXSupply products are covered by the manufacturer's warranty, ranging from 1 to 3 years depending on the brand. Warranty terms are fulfilled directly by the manufacturer.

If you experience any issue, contact us and we'll coordinate the claim process on your behalf.